Contents

06 10 08 CGs SERIES BOILER SUGGESTED SPECIFICATIONS I General Requirements A Furnish and install low pressure packaged sealed combustion power vented high Efficiency gas fired cast iron sectional boiler s that that can use outside air for combustion B Install boiler burner unit s in compliance with manufacturers installation instructions All work must be done in a neat and workman like manner C Weil McLain qty CGs boiler s size s capable of burning natural gas at 5 to 13 w c or propane 11 to 13 w c inlet pressure 1 Packaged boiler standard 2 High grade stainless steel burners for natural or propane gas firing 3 Water 4 Minimum 84 efficiency 5 Induced draft 6 Intermittent pilot with electronic module control w ...